DC Voltage Measurements:
- Unit Voltage: +/- 24VDC w/ 10mV resolution - System Voltage: +/- 600 VDC w/ 100mV resolution - Unit/System Accuracy: +/- 0.1% Full Scale - Unit in String Sensing: Auto and Manual
Impedance Measurement: - Load Current: Auto ranges 10, 5, 1 or 0.5 Amps at 216Hz for 2 seconds
- Unit Impedance: 1 uOhm to 85 mOhms w/ 1 uohm resolution
- Interconnect Impedance - Same as unit impedance - Impedance accuracy: +/- 10 uOhm - Impedance Multiplier Correction: +/- 0.1% - Cell Types: All from 2 to 16 VDC
- Calibration: Continually self calibrating AC offsets - Protection: Against over Voltage and Reversed Leads |
Power Requirements:
- 85-265 VAC 50-60Hz - Internal Rechargeable Battery - 12VDC Automobile charger Communications:
- Front: USB (Type B), Serial (DB-9F) Software: - BVM 4.1 Windows® based software package designed for Windows® XP and higher Environmental: - Operating: 0 to 40 deg C at 0 to 80% RH (non-condensing) - Storage: -20 to 60 deg C Enclosure: - Heavy Duty Aluminum w/handle Display - Blue LCD CE Mark Pending |